Model technical data

  • Mainly used for flexible materials of 5 mm thickness or less.
  • Suitable for M1 and M3 classification.

Physical specifications and utilities

Electrical supplyApprox. 220–240 V AC, 50/60 Hz, single phase; build-dependent.
Power / connected loadApprox. 1500–2500 W connected load for preliminary planning.
Overall instrument dimensionsApprox. 1000 × 800 × 1600 mm (W × D × H).
Instrument weightApprox. 80–140 kg net.
Gross / shipping weightApprox. 113–200 kg gross; estimated packing allowance.
Lab requirementsMethod-specified test gas, regulator and exhaust / fume hood; gas type and flow follow the selected method and burner.

Dimension order and approximate values are stated in each row. Packaging data are separate from instrument dimensions and net mass. Approx. rows are preliminary engineering estimates based on comparable equipment and function/capacity; they are not verified manufacturing measurements or standard requirements. Installation and shipment are finalised against the approved drawing and nameplate. Estimate scope: base product / one unit; external computer, bench and auxiliary plant excluded.

Specifications, dimensions, and power requirements are approximate and subject to change without prior notice for continuous design improvements.

Product technical specifications and images may vary according to manufacturing conditions and applicable standards.

Test and configuration

Measured output / function
Burning behaviour under radiant exposure
Parameters selected for the method
Radiant source, specimen geometry and auxiliary flame
Verification points
Burner/gas flow, geometry and timing

Listed methods are application references. Suitability is established by assessing the selected hardware, current method and calibration together.

Test parameters for the reviewed method

Values belong to the stated source edition. Test recipe, fixture and delivered instrument configuration are selected together.

NF P92-503:1995 · 4.1-4.6

  • Electric-burner method for flexible materials: specimen plane 30° to horizontal, nominal 500 W ceramic radiator and 600 × 160 mm support. Vertical gap from radiator top to specimen 30 ± 1 mm; verify pilot-flame arrangement separately. 500 W is radiator power, not total instrument power.

Control and recording specification

The following are method-specific software/recording requirements; delivered software modules are defined by the order scope.

  • Method code and edition, specimen ID, operator and selected test parameters are linked to the record.
  • The calculation and endpoint are defined by the selected method edition; instrument signals and operator assessments are kept distinct.
  • Raw measurements, units, valid/invalid test flags and the reported result remain traceable.
  • Calculations are checked against known inputs and an independent calculation; sensor channels are checked against calibration values.
Download the technical brochure (PDF)Revision: 27 October 2026

Test standards

Prices start from €18. Request the technical specification and a quotation for this instrument.

Request a quoteCall usPDF catalogue